Application of Acrel-2000 Power Monitoring System in Power Supply Equipment of General Practitioner Clinical Medium in Pingliang City

Introduce the power supply equipment project of the general clinical staff of Pingliang City, using intelligent power meters, collecting various electrical parameters and switching signals at the power distribution site. The system adopts the on-site local networking mode. After networking, it communicates through the fieldbus and travels to the background. Through the Acrel-2000 power monitoring system, the real-time monitoring and management of the power distribution circuit power distribution is realized.
Yang Junjun

1 Ankerui Electric Co., Ltd., Jiading, Shanghai 201801, China;



0. Overview

Pingliang City General Practitioner Clinical Media Project Pingliang City People's Hospital is located at No. 296, Jidong Road, Pingliang City, Gansu Province. It is the only third-grade hospital in Pingliang City, and is the largest medical, teaching and research institute in the city. Comprehensive hospitals for prevention and emergency rescue are health care centers and emergency care centers in Pingliang and Longdong.

This project mainly involves the PD7777-3S multi-function power meter of 18 Chint manufacturers installed in the transmission line of Pingliang People's Hospital and the important outlet circuit, and the NZL308M type of 57 Chint manufacturers installed on the ordinary outlet circuit. The unit intelligent measuring and controlling device, the monitoring host is located in the duty room next to the underground 1st floor of the power distribution room.

Demand analysis

In order to ensure the statistics and analysis of the electricity load for production management and real-time monitoring of dangerous sources. Real-time online monitoring of parameters such as voltage, current, and power in the incoming and outgoing circuits in the power distribution room at the project site is required. Once the monitoring point is abnormally monitored, the alarm can be detected in time, and the relevant personnel take necessary measures to avoid the occurrence of a safety accident. The automatic meter reading function saves manpower and material resources. The power trend curve function can intuitively display the working status and time of each loop, which is convenient for the user to find out the abnormal power circuit and timely rectify and establish the energy multi-level metering system to provide energy analysis basis. .

This technical condition applies to the power distribution room of Pingliang People's Hospital. Supplier products should be highly safe and reliable, easy to expand, and easy to maintain and maintain. The products provided by the supplier shall meet at least the technical conditions, but not limited to this, and its technical performance shall meet the requirements for data monitoring of the power distribution room.

data collection

Automatically collect analog data of all power meters in the field, and automatically collect switch data such as field switch status and fault status.

Support real-time acquisition, automatic cycle acquisition (timed acquisition) configurable cycle (1 minute to 24 hours).

Support data transmission correctness test, abnormal data automatic processing.

Support multi-thread processing mechanism, improve data collection efficiency, and can collect data for multiple devices at the same time.

The real-time display of the data adopts the visual display mode of the power distribution cabinet at one time, and the circuit breakers are disconnected and the fault status is visually visible.

Data analysis and processing

Comprehensive statistics and analysis of data need to achieve the following functions:

The statistics and calculations of the hours, days, months, and years of the electricity consumption data of each equipment.

The maximum, minimum, and average values ​​of the electrical load (active, reactive) of each device are calculated.

Count the electricity consumption (active, reactive) of each substation and the whole.

Data query and display

It is required to facilitate the query of the client and the query of the management personnel at all levels. The query interface can meet the requirements of managers at all levels and can support flexible conditional combination query and comparative analysis. The data of various statistical analysis can flexibly adopt various charts such as reports. Intuitive display function.

The data display function can be divided into three levels: operation layer, management layer and decision layer according to the different permissions of different users.

The operation layer has functions such as energy analysis, cumulative usage, real-time monitoring, operation record and ratio, comparison, and benchmark analysis.

The management has functions such as energy statistics and analysis, classification and classification, and benchmarking.

The decision-making layer has functions such as energy data analysis, data deletion, and database import/export.

authority management

It is required to assign different roles to different users, and can authorize function submenus, specific file records, data records, and the like.

The system requires a reasonable and complete user security control mechanism to effectively protect the information resources in the application environment and prevent information loss, theft and destruction.

Energy-saving renovation and effect evaluation

It is required to provide data support for energy-saving retrofits and to provide an evaluation of the effects before and after energy-saving retrofits.

parameter settings

The transformer transformer ratio can be set through the collection cabinet, and various current and voltage protection settings can be set.

Fault judgment and alarm have automatic fault diagnosis and use sound and light mode alarm function. The types of alarms include switch faults, voltage and current overruns, communication faults in the field acquisition module, and communication faults with the monitoring system. The alarm time is automatically recorded in the system database, which is convenient for users to inquire. The staff can grasp the real-time running status of the variable power station at any time, find the fault of the power distribution and operate accordingly, improve the management efficiency of the power distribution and improve the safety of the power system. reliability.

2. System plan

Acre-2000 Power Monitoring System According to the actual situation of Pingliang People's Hospital, the overall network structure is directly connected to the data collector through shielded twisted pair cable and then directly connected to the monitoring host of the power distribution room through the network cable to ensure power management monitoring. System transmission stability and real-time.

There are 18 PD7777-3S and 57 NZL308M in the field distribution room. 18 PD7777-3S multi-function power meters are connected to a serial port server with RS485 bus. 57 NZL308M unit intelligent measuring and controlling devices are connected to the serial port through two buses. On the serial port of the server, the serial server is connected to the monitoring room through the network cable to connect to the monitoring host to realize the data connection between the instrument on the bus and the monitoring host.

1) Station management

The management of the station control management system for the power monitoring system is a direct window for human-computer interaction. In the Xi'an Maternal and Child Health Hospital project, it mainly refers to the monitoring host placed in the power distribution room on the underground floor.

2) Network communication layer

The communication layer is mainly composed of a Nport5610-16, an Ethernet device and a bus network. The main function of the Nport5610-16 serial server is to monitor the on-site intelligent instrument; the main function of the Ethernet device and the bus network is to realize the data interaction between the substation and the main station, so that the distribution system management is centralized, informationized and intelligent. Greatly improve the safety, reliability and stability of the power distribution system, and truly achieve the goal of unattended.

3) Field device layer

The field device layer is a data acquisition terminal, which is mainly composed of smart meters. The smart meter is connected to the communication server through the shielded twisted pair RS485 interface, and uses the MODBUS communication protocol bus type connection to reach the communication host through the communication server. Implement remote control.

System structure diagram



China Hardware Business Network



Smart meter field connection

The field instruments are connected by hand-shielded through shielded twisted pair (RVSP2*1.0). The number of smart meters connected to each bus is about 20, different types of smart devices are connected to different buses, and then the data is uploaded to the serial port. The server Nport5430I, in turn, uploads the data to the local monitoring terminal. The specific connection diagram is as follows:



China Hardware Business Network



The PD7777-3S multi-function power meter of 18 Chint manufacturers installed on the incoming line and the important outlet circuit, and the intelligent monitoring and control device of the NZL308M unit of 57 Chint manufacturers installed on the ordinary outlet circuit can measure all conventional power parameters, such as: Three-phase voltage, current, active power, reactive power, power factor, frequency, active power, reactive power.

3. System function

The real-time monitoring system diagram of the substation is the main monitoring screen. The main operation status of all circuits in the substation is monitored in real time. Red represents the closing and green represents the opening. In the system diagram, you can visually see the operating parameters and status of each incoming and outgoing line. You can see all the conventional power parameters on the outgoing side of the transformer, such as: three-phase voltage, current, active power, reactive power, and power factor. , frequency, active power, etc. As shown below:



China Hardware Business Network



One system diagram



The remote signal and telemetry alarm function mainly completes the switch operation status and load line monitoring of the low-voltage outlet circuits. The switch position and load limit alarm pop-up alarm interface indicates the specific alarm position and audible alarm, reminding the on-duty personnel to deal with it in time. The load limit is freely set under the corresponding authority.



China Hardware Business Network



Current limit setting



The event alarm recording function mainly completes the alarm information event record and the occurrence time of the alarm time period, provides the basis for the on-duty personnel and analyzes the cause of the accident.

The parameter meter reading function mainly queries the electric parameters of the low-voltage outlet circuits. Supports electrical parameter query at any time, with functions such as data export and report printing. The report queries the electrical parameters of the low-voltage circuits in the power distribution room of Pingliang City People's Hospital, including: three-phase current, active power and active power. The loop name of the report is associated with the database, which is convenient for the user to modify the loop name. As shown below:



China Hardware Business Network



Electrical parameter reading



The power consumption report function can select the time period for query, support the electricity cumulative query for any time period, and have the functions of data export and report printing. Provide accurate and reliable energy reports for duty personnel. The loop name of the report is associated with the database, which is convenient for the user to modify the loop name. As shown in the figure below, the user can directly print the report and save it to another location in EXCEL format. As shown below:



China Hardware Business Network



Energy report



The schematic diagram of the system communication structure mainly shows the networking structure of the system. The system adopts a layered distributed structure and monitors the communication status of the interval layer devices. Red indicates normal communication and green indicates communication failure. The following figure shows the state of the substation communication.



China Hardware Business Network



Communication structure diagram



The load trend curve interface can be used to visually check the load operation of the loop. View real-time and historical trend curves, click the corresponding button or menu item on the screen to complete the corresponding function switching; help users to enter the trend analysis and fault recall, with curve printing function. Provides intuitive and convenient software support for analyzing the health of the entire system. As shown below:



China Hardware Business Network



Trend graph



4 Conclusion

In the application of power distribution facilities today, the distribution safety of hospital projects is very important. The application of the Acrel-2000 power monitoring system introduced in Pingliang City People's Hospital can realize the power supply to the power distribution and distribution circuit of the power distribution room. Real-time monitoring, the system analyzes and processes the collected data, displays the running status of each distribution circuit in the distribution room in real time, pop-up alarm dialog box, voice prompt for the load limit, and generates various energy reports, analysis curves, graphics, etc. It is convenient for remote meter reading and analysis and research of electric energy. The system is safe, reliable and stable. It provides a real and reliable basis for solving the problem of electricity use and achieves good enterprise benefits.



references:

[1] "Guidelines and Application Guidelines for Digital Measurement of Electric Power Measurement", Ren Zhicheng, Zhou Zhong, China Electric Power Press

[2] "Application of Power Monitoring System in Power Supply and Distribution Design", Gao Shihong, Science and Technology Wind [3] "Power Monitoring for 10kv Power Supply and Distribution Design", Yao Qiang, Technology World

About the Author

Yang Junjun, female, undergraduate. Position: Now working for Ankerui Electric Co., Ltd., contact number, mobile phone, QQ
Http://news.chinawj.com.cn Editor: (Hardware Business Network Information Center) http://news.chinawj.com.cn

Gateball Astro Turf