Commissioning of cabinet centrifugal fan
1. The fan allows full-voltage starting or step-down starting, but it should be noted that the current at full-voltage starting is about 5~7 times of rated current. The step-down starting torque is proportional to the square of the current. When the grid capacity is insufficient, Use a step-down start. (When the power is greater than 11KW, it is recommended to use a step-down start.)
2. When the fan is in the test run, the product manual should be read carefully to check whether the wiring method is consistent with the wiring diagram; the working voltage of the supplied fan power supply should be carefully checked whether the power supply voltage meets the requirements, whether the power supply is out of phase or in phase, and the capacity of the distributor component is Meet the requirements.
3. The number of people in the test is not less than two. One person controls the power supply. One person observes the operation of the fan and immediately detects the abnormal phenomenon. First check whether the direction of rotation is correct. After the fan starts running, check whether the running current is balanced and whether the current is current. Exceed the rated current; if there is no normal phenomenon, stop the inspection. After five minutes of operation, check whether the fan is abnormal or not, and confirm that there is no abnormal phenomenon and then start up.
4. When testing the two-speed fan, start the low speed first and check whether the rotation direction is correct. When the high speed is started, it must be restarted after the fan is stationary to prevent the high speed reverse rotation, causing the switch to trip and the motor to be damaged.
For details, please refer to the website: mixed flow fan, cabinet centrifugal fan, fire exhaust fan http://
Our LED Emergency Batten Light is perfect for commercial and industrial use, made from solid polycarbonate with a thick poly carbonate diffuser the unit is very durable this fitting has an IP rating of 65 and is anti corrosive. Interal lithium battery pack to make emergency time rating from 60-180mins. The fitting gives off an impressive 5850 lumens using only 65 watts of energy making it a great energy saving light fitting. The batten uses high quality LED chips giving off a great array of light to any indoor and outdoor area.
Emergency Batten Light,Emergency Led Batten,Emergency Light Batten,Led Emergency Batten Light
Foshan Nai An Lighting Electric Co.,ltd , https://www.emballast.com